Product Description:

  • Designed to have low pressure drop and higher efficiency
  • Copper “Tube in Tube” non-corrosive heat exchanger, designed to have lower pressure drop and higher efficiency contains in built centrifugal moisture separator having dead zone to avoid carry over of condensate.
  • PUF insulation for heat exchanger assembly.
  • PUF Insulation for Heat Exchanger Assembly.
  • Electronic timer operated Auto Drain Valve.
  • Universally available refrigeration components like Compressor, Fan motor, Filter dryer, Expansion Valve etc.
  • Non-cyclic refrigeration systems, with the help of hot gas bye pass Solenoid Valve, for varying load condition and seasonal adjustments.
  • GEM PET Series Dryers are filled with “Ozone Friendly” R134a refrigerant.

Product USP:

  • Complete range with ozone friendly refrigerant
  • Compact in size
  • Wide range
  • Lower power consumption
  • Reliable components
  • Consistent dew point

Technical Specifications

Base MODELAir FlowRef. PowerElectrical Connection*Inlet / OutletDimensions (mm)Weight
CFMm³/hkW*220V / 1Ø/50Hz415V / 3Ø/50HzBSPABCkg.
2KD002720340.21½”36047555045
2KD004740680.36½”36047555047
2KD0067601000.36½”36047555047
2KD0087801360.481″50060073078
2KD01071001700.601″50060073090
2KD01571502550.681″50060073090
2KD02072003401.01½”700700830120
2KD02572504251.41½”700700830135
2KD03073005101.41½”700700830135
2KD04074006801.82″9009001230170
2KD05075008502.22″ NB flg9009001230180
2KD075775012753.32″ NB flg75010001400250
2KD1007100017004.22″ NB flg90012001475350

* Voltage 180 to 240 V in case of 1Ø; 380 to 450 V in case of 3Ø

# Power Consumption considering 45° C inlet and 35° C ambient temp.

Note: For70 to 80 bar operating pressure, contact factory

SIZING CONVERSION FACTORS:

Inlet Temperature (C1)
Temperature °C30354045505560
Correction Factor1.21.151.051.00.850.70.6
Ambient Temperature (C2)
Temperature253035404550
Correction Factor1.21.151.11.051.01.9
Inlet Pressure (C3)
Inlet Pressurebar (g)45678910.51112.513141516
psi (g)587387100116131150160180189200218232
Correction Factor0.750.850.951.001.061.041.071.181.091.221.121.251.14
Dew Point (C4)
Dewpoint in C3710
Correction Factor.01.151.3

Dryer Normal Capacity = Actual Capacity × C4/C1 × C2 × C3

Operating conditionsIdealMaximum
Inlet temperature45°C60°C
Ambient Temperature35°C50°C
Working pressure40 bar42 bar
Pressure Dew point3°CNIL

* Product Design and specification subject to change due to constant upgradation.