Product Description:
- Designed to have low pressure drop and higher efficiency
- Copper “Tube in Tube” non-corrosive heat exchanger, designed to have lower pressure drop and higher efficiency contains in built centrifugal moisture separator having dead zone to avoid carry over of condensate.
- PUF insulation for heat exchanger assembly.
- PUF Insulation for Heat Exchanger Assembly.
- Electronic timer operated Auto Drain Valve.
- Universally available refrigeration components like Compressor, Fan motor, Filter dryer, Expansion Valve etc.
- Non-cyclic refrigeration systems, with the help of hot gas bye pass Solenoid Valve, for varying load condition and seasonal adjustments.
- GEM PET Series Dryers are filled with “Ozone Friendly” R134a refrigerant.
Product USP:
- Complete range with ozone friendly refrigerant
- Compact in size
- Wide range
- Lower power consumption
- Reliable components
- Consistent dew point
Technical Specifications
Base MODEL | Air Flow | Ref. Power | Electrical Connection* | Inlet / Outlet | Dimensions (mm) | Weight | ||||
CFM | m³/h | kW* | 220V / 1Ø/50Hz | 415V / 3Ø/50Hz | BSP | A | B | C | kg. | |
2KD0027 | 20 | 34 | 0.21 | – | ½” | 360 | 475 | 550 | 45 | |
2KD0047 | 40 | 68 | 0.36 | – | ½” | 360 | 475 | 550 | 47 | |
2KD0067 | 60 | 100 | 0.36 | – | ½” | 360 | 475 | 550 | 47 | |
2KD0087 | 80 | 136 | 0.48 | – | 1″ | 500 | 600 | 730 | 78 | |
2KD0107 | 100 | 170 | 0.60 | – | 1″ | 500 | 600 | 730 | 90 | |
2KD0157 | 150 | 255 | 0.68 | – | 1″ | 500 | 600 | 730 | 90 | |
2KD0207 | 200 | 340 | 1.0 | – | 1½” | 700 | 700 | 830 | 120 | |
2KD0257 | 250 | 425 | 1.4 | – | 1½” | 700 | 700 | 830 | 135 | |
2KD0307 | 300 | 510 | 1.4 | – | 1½” | 700 | 700 | 830 | 135 | |
2KD0407 | 400 | 680 | 1.8 | – | 2″ | 900 | 900 | 1230 | 170 | |
2KD0507 | 500 | 850 | 2.2 | – | 2″ NB flg | 900 | 900 | 1230 | 180 | |
2KD0757 | 750 | 1275 | 3.3 | – | 2″ NB flg | 750 | 1000 | 1400 | 250 | |
2KD1007 | 1000 | 1700 | 4.2 | – | 2″ NB flg | 900 | 1200 | 1475 | 350 |
* Voltage 180 to 240 V in case of 1Ø; 380 to 450 V in case of 3Ø
# Power Consumption considering 45° C inlet and 35° C ambient temp.
Note: For70 to 80 bar operating pressure, contact factory
SIZING CONVERSION FACTORS:
Inlet Temperature (C1) | |||||||||||
Temperature °C | 30 | 35 | 40 | 45 | 50 | 55 | 60 | ||||
Correction Factor | 1.2 | 1.15 | 1.05 | 1.0 | 0.85 | 0.7 | 0.6 |
Ambient Temperature (C2) | |||||||||||
Temperature | 25 | 30 | 35 | 40 | 45 | 50 | |||||
Correction Factor | 1.2 | 1.15 | 1.1 | 1.05 | 1.0 | 1.9 |
Inlet Pressure (C3) | ||||||||||||||
Inlet Pressure | bar (g) | 4 | 5 | 6 | 7 | 8 | 9 | 10.5 | 11 | 12.5 | 13 | 14 | 15 | 16 |
psi (g) | 58 | 73 | 87 | 100 | 116 | 131 | 150 | 160 | 180 | 189 | 200 | 218 | 232 | |
Correction Factor | 0.75 | 0.85 | 0.95 | 1.00 | 1.06 | 1.04 | 1.07 | 1.18 | 1.09 | 1.22 | 1.12 | 1.25 | 1.14 |
Dew Point (C4) | |||||||||||
Dewpoint in C | 3 | 7 | 10 | ||||||||
Correction Factor | .0 | 1.15 | 1.3 |
Dryer Normal Capacity = Actual Capacity × C4/C1 × C2 × C3
Operating conditions | Ideal | Maximum |
Inlet temperature | 45°C | 60°C |
Ambient Temperature | 35°C | 50°C |
Working pressure | 40 bar | 42 bar |
Pressure Dew point | 3°C | NIL |